Thermostat not turning on boiler in one of the zones. Thermostat not the issue, it’s been replaced. Didn’t need to bleed the line but I did just to make sure. All other zones work fine. Also switches out the older taco valve to see if that was the issue—no dice. Not breaker issues either.
So I’m thinking some electrical connection issue somewhere in the heating system. The thermostat turns on the AC/Fan no problem.
The battle continues!
did you install thermostat yourself? what kind of thermostat and when? did it happen after the installation or before?
Please Login to reply.
Happened before. Swapped out the original Honeywell with another one and same results, they both can control AC but not baseboard heat in that zone.
definitely not thermostat and it’s just electrical. again, should be really simple, but definitely would not do it by yourself.
🙏🫂