20 gauge wire and 20 amp circuit.

Reply to this note

Please Login to reply.

Discussion

dafuq? who put in 20 gauge. surprised the house didnt burn down

Well then maybe I'm wrong. This was just put in 9 years ago.

what color is the outer sheathing containing the wires

yellow. awg 12 cu 2 cdr with awg 12 ground 600 volts.

ok. suitable for 20 amp. just browning from prolonged use. buy and install a quality receptacle

Thank you. These receptacles are just Walmart cheapies. I'll replace with a better quality. Thank you again.

That was my 1st thought. Throw in some 12-2 and replace the outlet with an AFCI. GFCI is great but if the arc doesn't cause a ground the power will stay live.

Hell my house was built & wired pre building code & I have 12 gauge in the walls. No grounds though funny enough